Chinese Professional Generator Set Manufacturers
15
2025
-
08
What are the reasons for causing high water temperature alarm shutdown and inability to use?
Author:
Water tank leakage or insufficient water volume; The water temperature sensor is damaged;
Water tank leakage or insufficient water volume; The water temperature sensor is damaged; The dirt in the water tank and waterway is too thick, or there is too much oil pollution on the heat sink;
Excessive wear of fan belt and insufficient pressure; Wear and tear of the water pump, insufficient water flow of the pump; The thermostat opening angle is not sufficient and there is a jamming phenomenon; The damaged water channel of the cylinder gasket is connected to the cylinder; The cylinder liner is severely worn and partially leaking water; The ventilation in the computer room does not meet the requirements; Engine overload operation; Excessive fuel supply (including engine fatigue)